DRAKA Instrument Cable(IS-Blue) - FIre Resistant - Individual Screen - Armoured(SWA) CU/MGT/XLPE/ISOS/LSHF/SWA/LSHF-AT-AR 500V to BS EN50288-7, IEC332-3-22, IEC 60331-21
DRAKA Instrument Cable(IS-Blue) - Fire Resistant - Individual Screen - Armoured(SWA)
CU/MGT/XLPE/ISOS/LSHF/SWA/LSHF-AT-AR 500V to BS EN50288-7,
IEC60332-3-22, IEC 60331-21
Application
Instrumentation cables are used in data processing and process control. The individual screening of the pairs guarantee high cross-talk attenuation. The electrostatic screen protect the screened pairs against outer electrostatic interference fields. Low level of line attenuations and low mutual capacitances enable long transmission distances fast pulse accelerations in damp locations, in open spaces and for underground laying. The cables are mainly used in petroleum and petrol chemical industry. Incorporation with layer of fire proof barrier, these cables are mainly used for those critical areas that require circuit integrity in the emergency systems such as emergency exit lights, emergency lifts, sprinkles, smoke and heat detectors etc.
Cable Structure & Features
Technical Data
CU/MGT/XLPE/ISOS/LSHF/SWA/LSHF-AT-AR 500V to BS EN50288-7,
IEC60332-3-22, IEC 60331-21
Application
Instrumentation cables are used in data processing and process control. The individual screening of the pairs guarantee high cross-talk attenuation. The electrostatic screen protect the screened pairs against outer electrostatic interference fields. Low level of line attenuations and low mutual capacitances enable long transmission distances fast pulse accelerations in damp locations, in open spaces and for underground laying. The cables are mainly used in petroleum and petrol chemical industry. Incorporation with layer of fire proof barrier, these cables are mainly used for those critical areas that require circuit integrity in the emergency systems such as emergency exit lights, emergency lifts, sprinkles, smoke and heat detectors etc.
Cable Structure & Features
Conductor | (Cu) Plain annealed stranded copper conductor Class 2, IEC 60228, BS6360 |
Fire proof layer | (MGT) Mica glass tape |
Insulation | (XLPE) Cross-linked Polyethylene |
Pairing / Twining | Two/Three/Four insulated cores are cabled together and covered with a polyester tape wrapping |
Individual screen | (IS) Min. 20% overlap of aluminium backed polyester tape in contact with 0.5mm² (16/0.20mm) tinned annealed drain wire followed by a polyester tape wrapped over the screening tape |
Assembly | Multiple pairs/triads/quads are cabled together, supplied with non-hygroscopic filler (optional) to obtain a circular construction and covered with a polyester tape wrapping |
Overall Screen | (OS), Min. 20% overlap of aluminium backed polyester tape in contact with 0.5mm² (16/0.20mm) tinned annealed drain wire followed by a polyester tape wrapped over the screening tape |
Bedding | (LSHF) Low Smoke Halogen Free -Black |
Armouring | (SWA) Galvanized Steel Wire Armour |
Outer Sheath | (LSHF-AT-AR) Low smoke zero halogen compound with anti-termite and anti-rodent additives. Black (Optional: Blue colour for Intrinsically Safe) |
Insulation color |
1 pair in Black & White 2 pair & above -each pair in Black & White core with numbering. 1 triad in Black, White & Red 2 triad & a bove –each triad in Black, White & Red printed with numbering. |
Technical Data
Reference Standard | BS EN 50288-7 |
Voltage | 500V |
Max Operating Temperature | +90ºC |
Halogen Free | IEC 60754 |
Low Smoke Emission | IEC 61034 |
Fire Integrity | IEC 60331-21 |
Flame Retardant | IEC 60332-3-22 |
Max. Conductor Resistance |
≤7.6Ω/km at 20°C(2.5mm²) ≤12.3Ω/km at 20°C(1.5 mm²) ≤18.4Ω/km at 20°C(1.0 mm²) ≤26.5Ω/km at 20°C(0.7 5mm²) |
Max. Mutual Capacitance(at 1 KHz) |
≤ 85pF/min (1.5-2.5 mm²) ≤ 75pF/min (0.5-1.0 mm²) |
Max. L /R Ratio |
≤ 40pF/min (1.5-2.5 mm²) ≤ 25pF/min (0.75-1.0 mm²) |
Test Voltag | 2000Vac for 1 minute |
Bending Radius |
10 x overall diameter |