FABER KABEL Silicone Cable 300/500V SIHF-J
FABER KABEL Silicone Cable
300/500V SIHF-J
Application
Heat and coldness resistant power, control and connecting cable in electrical facilities, for fixed laying and flexible applicationswithout tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms and outdoor use, no layingunderground.
Cable Structure & Features
Technical Data
300/500V SIHF-J
Application
Heat and coldness resistant power, control and connecting cable in electrical facilities, for fixed laying and flexible applicationswithout tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms and outdoor use, no layingunderground.
Cable Structure & Features
Conductor material | Copper strand tinned |
Conductor class | Acc. to DIN VDE 0295 class 5 resp. IEC 228 class5 |
Core insulation | Silicone |
Core identification | Up to 5 cores acc. to DIN VDE 0293-308 cores; colour code with or without green/yellow |
Stranding | Stranded in layers |
Outer sheath | Silicone |
Sheath colour | Redbrown |
Special Features / Remarks | |
|
Technical Data
Standard | Acc. to DIN VDE 0282 part 1 and HD22.1 |
Rated voltage | Uo/U: 300/500 V |
Testing voltage | 2Kv |
Conductor resistance | At +20°C acc. to DIN VDE 0295 class 5 resp. IEC 228 class 5 |
Insulation resistance | Min. 2.0 GΩx km |
Current carrying capacity | Acc. to DIN VDE refer to Technical Guideline |
Min. bending radius fixed | 4 x d |
Min. bending radiu moved | 6 x d |
Operat. temperature | fixed: - 60°C / +180°C; short-time: +200°C |
Temp at conductor+180°C | Halogen freeacc. to VDE 0472 part 813 and IEC754-1 |
Burning behavior | Self-extinguishing and flame retardant DIN VDE0482 part 265-2-1 (IEC 60332-1-test B) |